Productos -> Sensores / Transductores / Acondicionadores -> Potencia Eléctrica -> Medición de Variables Eléctricas -> S203T /S203TA
Características:
S203T / S203TA
Analizador de rojo trifásico con comunicación Modbus RS485.
Características:
- Entrada de hasta 600 Vac, 5A rms (S203TA), 100mA (S203T)
- Salida de corriente de 0 a 20, 4 a 20 mA o voltaje de 0 a 5, 0 a 10 Vdc
- Interfaz RS485 con comunicación serial Modbus-RTU, salida análoga configurable a Vrms, Irms, Watt (bi-direccional)
- Precisión de 0.5% (S203TA), 0.2% (S203T)
- Aislamiento galvánico @3.75KV
- Montaje a Riel DIN
- Alimentación de 10 a 40 Vdc, 19 a 28 Vac
Technical specifications | |
TECHNICAL SPECIFICATIONS | |
Power Supply | 10-40 Vdc, 19-28 Vac (50-60 Hz) |
Power consumption | 2,5 W |
Isolation | 4 kVac between input measurement and other circuits 1.500 Vac between power supply and communication // retransmitted output |
Installation Category | 350 V CAT II |
Status indicator | Power supply, Fail, RS485 communication |
Retransmission error | 0,1% (full range) |
Band-Pass | 7 kHz |
Accuracy class | 0,2% |
Insertion Type | 1- phase, 3-phase Aron, 3- phase with 4 wires |
Connections | Rogowsky sensors with output max 200 mV RMS |
Protection Degree | IP20 |
Mounting | 35 mm DIN rail guide |
Connection | Screw terminal, pitch 5,08 mm |
Operating Temperature | -10..+65°C S203RC-D, -20...+70°C Rogowski sensor |
Dimensions [W*H*D] | 105 x 89 x 60 mm |
Weight | 200 g |
Enclosure | Plastic Material UL V0 |
COMMUNICATION | |
Interface | RS485, 2 wire |
Speed | Sampling time 25 ms |
Protocol | ModBUS RTU slave |
Distance | Up to 1.200 m |
Connectivity | Max. 32 nodes |
I/O | |
Channels Numbers | 1 input, 2 output (Baud Rate max 115.200 b/s) |
Input Type | VOLTAGE up to 600 Vac (50-60 Hz); CURRENT from Rogowski transducers with max output 200 mV |
Output Type | n° 1 RS485 output modbus slave n° 1 analogue output, voltage/current (Voltage 0..5, 0..10Vdc, min load resistance 2KOhm. Current 0..20, 4..20mA, max load resistance 500 Ohm) n° 1 digital output (pulse for produced/ consumed energy or to report the direction of the current) |
PROGRAMMING | |
Configuration | DIP-switch or software (EASY SETUP) |
STANDARD | |
Approval | CE |
Norms | EN 61000-6-4, EN 61000-6-2, EN 61010-1 |