Inputs
  • Input range ±50mV to ±50V, 500Vpk with attenuator probe
  • Base accuracy 0.05%
  • Up to 8 channels (up to 32 channels with expansion modules)
  • Flexible triggering allowing any channel combination or with specific input conditions
  • Single ended or differential inputs
  • 16 bit resolution

Powerful measurement capability in one compact unit

  • Portable PC based data acquisition and recording system
  • Transient recorder
  • High speed data logging
  • Very long recording memory
  • High resolution measuring inputs
  • Comprehensive analysis software includes DSO, Spectrum Analyser and Math capability

System capability

  • 16 MWord/ch logging memory
  • Up to 80MHz sampling
  • 80GByte Hard Disk
  • 1GByte memory
  • DVD writer
  • 100Mbit Ethernet
  • USB 2.00

About TransLog
The TransLog is a notebook size high speed transient data recorder, containing up to 8 channels. TransLog has a wide range of uses, especially in data logging applications where many signals must be examined and recorded simultaneously. Often triggering from one or more of its inputs, TransLog makes it possible to capture fast transient events that would normally be missed. High resolution and large memory ensures that events can be recorded accurately over long periods and magnified as required. Multiple cursors and colour traces, allows the user quick and easy analysis in terms of time and amplitude. Long pre-trigger and post-trigger memory allows detailed examination of events before and after the main trigger, ensuring measurement data is not lost. A large 14.1" TFT screen ensures clear viewing without connecting to an external display or PC. Recorder mode offers direct storage to hard disk at rates of 15MHz. Data can be stored in a number ways and the storage capability is enhanced using 100Mbit Ethernet or USB 2 interfaces.

TraNET Transient Recorder PC Rack Systems

 
Custom system based on 32 differential channels

The TraNET is ideal for configuring large multi channel systems but based on the TransLog measurement performance and specification Up to 32 differential channels per PC rack Up to 64 single ended channels per PC rack TraNET PC rack systems can be linked to allow greater than 64 transient recorder channels Ethernet comms and control for Networking Mouse & keyboard are supplied, external monitor is required

Typical applications
  • Crash Testing
  • Shock wave and shock experiments in pipes (more channels can be added using an external housing)
  • Materials testing
  • Military industries and military research institutes measuring pressures during detonation or blast, speed of missiles (up to 10000m/s)
  • Applications where the TransLog is used instead of an high sampling 4 channel oscilloscope, like sonar, ultrasonics and motor drives
  • Ultrasonic imaging systems like Sonar
  • PWM motor drives and ac drive systems 
  • Examination of low voltage switches, protection relays and circuit breakers
  • Disturbance capture
  • Service tool for power station and power distribution
 
TransLog and TraNET Specifications
Model 8014-4/8
8016-4/8
4014-4/8
4016-4/8
2014-4/8
2016-4/8
1014-4/8
1016-4/8
 
Input Channels

4 Single-Ended or  2 Differential software switchable

4/8 Single-Ended or 2/4 Differential software switchable
ADC-Resolution

14 Bit or 16 Bit (16 Bit up to 1/8 of the max sampling rate)

Max. Sampling Rate

4/8 x 80 MHz (12.5ns)

4/8 x 40 MHz (25ns)

4/8 x 20 MHz (50ns)

4/8 x 10 MHz (100ns)
Memory Length

4 x 16MWords, 8 x 8MWords (= 128Mbytes)
optional up to total of 256Mwords (=512Mbyte)

Input Amplifier
Ranges
(1-2-5 Steps)

+/-50mV .. +/-50V or 0.1V .. 100V (100V limited at 70V)

Adjustable Offset

0...100% in in steps of 0.1% selectable by software

Input-Impedance

1 MOhm (+/-0.2%) / 40pF (+/-5%)

Input-Coupling

AC / DC switchable by software (AC: -3dB at < 5Hz).  Inputs can be inverted

Bandwidth

30 MHz ( 8 MHz ranges < 1V )

18 MHz ( 7 MHz ranges < 1V )

10 MHz ( 6 MHz ranges < 1V )

5 MHz ( 4 MHz ranges < 1V )

Slew rate (10..90 %) 16ns ( 50ns ranges < 1V )

25ns ( 60ns ranges < 1V )

40ns ( 70ns ranges < 1V )

70ns ( 80ns ranges < 1V )20 MHz

Settling time to 1%

< 200ns

Lowpass-Filter (RC)

2 settings, 1 MHz, 100kHz, OFF - software selectable

Anti-Aliasing-Filter

Optional: 200 Hz ... 5 MHz 4th order Butterworth - software selectable

Common Mode Range

Differential-Mode: +/-8V and +/-80V ranges >5V

Common Mode Rejection

>74dB (DC...1kHz); >60dB (...100kHz); >40dB (...5MHz)

Range Error (+/-)

max. 0.1% typ. 0.03% (with auto calibration)

Offset Error (+/-)

max. 0.1% typ. 0.02% (with auto calibration)

Offset Drift (+/-)

max. 0.010%/°C, typ. 0.005%/°C
(compensation possible by auto calibration)

Input Noise at max sample rate
5MHz sample rate
1MHz sample rate
100kHz sample rate
10kHz sample rate
< 0.300mVrms
< 0.150mVrms
< 0.100mVrms
< 0.050mVrms
< 0.025mVrms
< 0.200mVrms
< 0.120mVrms
< 0.070mVrms
< 0.030mVrms
< 0.015mVrms
< 0.150mVrms
< 0.100mVrms
< 0.050mVrms
< 0.020mVrms
< 0.010mVrms
< 0.150mVrms
< 0.100mVrms
< 0.050mVrms
< 0.020mVrms
< 0.010mVrms
Signal-to-noise (SNR)
with RC-Filter
Max sample rate
10MHz sample rate
5MHz sample rate
1MHz sample rate
100kHz sample rate
10kHz sample rate
59dB
62dB
66dB
69dB
79dB
89dB
62dB
68dB
70dB
74dB
82dB
90dB
67dB
70dB
72dB
76dB
84dB
92dB
70dB
70dB
72dB
76dB
84dB
92dB
Channel isolation / cross talk attenuation at 10kHz

> 80dB (>60dB on ranges <1V)

Special:
Auto Calibration

Automatic adjustment of gain and offset in all ranges (execution by software)

Trigger
Trigger Channels

4 or 8 respectively on Analog-inputs, pos/neg slope, with or without hysteresis, Window-IN, Window-OUT

External Trigger Input

1 per system (TTL), pos. or neg. Slope

Trigger Delay

-100% (Pretrigger) to +200% (Posttrigger) in 1% steps

Miscellaneous
Digital-Inputs (Marker) 14 Bit modules only - available as an option

Optional 8 or 16 (up to 2 per analog channel) TTL

Hard disk-Recording
(Chart-Recorder-Mode)

Sum sampling rate up to 15MHz

Ext. Control Inputs (TTL)

Trigger, Arm/Disarm, ext. Sampling rate (fmax = 1/4 max. sampling rate)

Status-Outputs (TTL)

Trigger-Output, Record-Active (indicates recording state)

PC System
Display

14,1" TFT, XGA (1024 x 768)

Processor

Pentium IV, 2 GHz

Memory

1 GB

Harddisk

80 GB

Drives

DVD RW-ROM,

Interfaces

2 x RS232, 2 x USB 2.0, Ethernet, Printer, Monitor

Operating system

Windows Xp Professional

Housing
Type

"Shell in a Shell" housing technology incl. carrying bag

Dimensions

W x H x D 40.01 x 28.58 x 19.79 cm

Weight

9.5 Kg

Environmental
Power

100V – 240 V AC +/-5% / 47 – 63Hz and 400 Hz

Temperature

Operating: 0°C – 45°C
Non-operating: -10°C – 70°C

Humidity

Up to 85% non condensing

Shock

10g 11ms 1 sine

Vibration (IEC 68-2-6)

3 – 500Hz 0.41g

 

Ordering a TransLog 14 bit system

Type Channels Sampling Resolution Memory/Ch
TransLog-1014-4S 4 up to 10MHz 14 Bit 16Mword
TransLog-1014-4D 4 up to 10MHz 14 Bit 16Mword
TransLog-1014-8S 8 up to 10MHz 14 Bit 8Mword
TransLog-1014-8D 8 up to 10MHz 14 Bit 8Mword
TransLog-2014-4S 4 up to 20MHz 14 Bit 16Mword
TransLog-2014-4D 4 up to 20MHz 14 Bit 16Mword
TransLog-2014-8S 8 up to 20MHz 14 Bit 8Mword
TransLog-2014-8D 8 up to 20MHz 14 Bit 8Mword
TransLog-4014-4S 4 up to 40MHz 14 Bit 16Mword
TransLog-4014-4D 4 up to 40MHz 14 Bit 16Mword
TransLog-4014-8S 8 up to 40MHz 14 Bit 16Mword
TransLog-4014-8D 8 up to 40MHz 14 Bit 16Mword
TransLog-8014-4S 4 up to 80MHz 14 Bit 16Mword
TransLog-8014-4D 4 up to 80MHz 14 Bit 16Mword
TransLog-8014-8S 8 up to 80MHz 14 Bit 16Mword
TransLog-8014-8D 8 up to 80MHz 14 Bit 16Mword